MISSION CRITICAL Air Conditioning Systems Series 7 Guide Specification – 60 Hz ClimateWorx International Inc. S7-GS-602014.doc 2014 14 Chel
Series 7 Guide Specification-60 Hz 6.4.2 To achieve the tightest control tolerance and minimize component on/off, the units shall have a built in co
Series 7 Guide Specification-60 Hz 2 S7-GS-602014.doc 2014
Series 7 Guide Specification-60 Hz 1. General 1.1 The intelligent precision air-conditioning system shall be a ClimateWorx Series 7 model _____ .
Series 7 Guide Specification-60 Hz 2.2.5 The fan motor shall be an open permanent split capacitor type. 2.3 Filter 2.3.1 The filter chamber shall
Series 7 Guide Specification-60 Hz 3.1.3 The refrigeration circuit shall be pre-piped and leak tested ready for field connection. 3.1.4 All refrige
Series 7 Guide Specification-60 Hz 3.4.6 The winter control system for the air cooled condenser shall be refrigerant head pressure control (heated
Series 7 Guide Specification-60 Hz 5. Control System 5.1 Standard System 5.1.1 The unit shall use a single stage, heat/cool, remote wall-mounted 7
Series 7 Guide Specification-60 Hz 6.2 Control Features 6.2.1 System set points and configuration shall be programmable only when access is gained
Series 7 Guide Specification-60 Hz 6.2.9 The system shall have a temperature and humidity scatter graph which shows the main temperature and humidit